IMPORTANT!

Please check that the cables are connected and torqued properly.
Use 90℃ copper conductors only.

XP100U-H2

XP100U-H4

XP83U-H6

XP90U-H6

XP100U-H6

AC connection cable

A, B, C, N and PE

Nominal AC voltage

208V

480V

600V

600V

600V

Maximum AC current

278A

120A

80A

87A

96A

XP100U-H4/ XP83U-H6/ XP90U-H6/ XP100U-H6

Number of GRID cables

Cable Size

Torque

A, B, C, N

4

1AWG

All 194℉(90℃) copper wire, 40 lb-ft

tightening torque

PE

1

4AWG

194℉(90℃) copper wire, 40 lb-ft

tightening torque