IMPORTANT!
Please check that the cables are connected and torqued properly.
Use 90℃ copper conductors only.
XP100U-H2
XP100U-H4
XP83U-H6
XP90U-H6
XP100U-H6
AC connection cable
A, B, C, N and PE
Nominal AC voltage
208V
480V
600V
600V
600V
Maximum AC current
278A
120A
80A
87A
96A
XP100U-H4/ XP83U-H6/ XP90U-H6/ XP100U-H6
Number of GRID cables
Cable Size
Torque
A, B, C, N
4
1AWG
All 194℉(90℃) copper wire, 40 lb-ft
tightening torque
PE
1
4AWG
194℉(90℃) copper wire, 40 lb-ft
tightening torque