Caution, Burn, Hazard – KACO XP83U-H6 (Canada) User Manual
Page 3: Information

Page 3
CAUTION!
"CAUTION" indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
BURN
HAZARD!
Do not touch. The Inverter contains components that become hot during normal operation.
Other Symbols
INFORMATION!
This symbol accompanies notes that you should know and use to ensure optimal operation of the system.
Wiring Requirements
All wiring methods and materials shall be in accordance with the National Electrical Code ANSI/NFPA 70, as
well as all state and local code requirements. Cable sizes in the chart below are the minimum. Because the
field connections are bus bars for accepting crimp lugs, larger cables can be used if needed.
Grid Connection
XP100U-H4/ XP83U-H6/ HP90U-H6/ XP100U-H6
Number of GRID cables
Cable Size
Torque
A, B, C, N
4
1AWG
All 194℉ (90℃) copper wire, 40 lbs-ft
tightening torque
PE
1
4AWG
194℉ (90℃) copper wire, 40 lbs-ft
tightening torque