Each cable is related to certain polarity.
During cable connection, make sure that the cable is connected to the proper location

DC Port for Negative ground system

DC Port for Positive ground system

IMPORTANT!

Please check if all cables are securely fastened and torqued.
Use copper conductors only.
Check that all conduit fittings are installed correctly.
Check that all fittings are sealed correctly if installed outdoors.

XP100U-H2/ XP100U-H4/ XP100U-H6

XP83U-H6

XP90U-H6

Number of strings

1, 2, 3 or 4 (1 fuse is standard and 2, 3, or 4 fuses are optional)

DC input voltage

300V ~ 600V

Maximum DC current

350A

290A

317A

XP100U-H2/ XP100U-H4/ XP83U-H6/ XP90U-H6/ XP100U-H6

Number of PV strings

Cable Size

Torque

Hot, Return

1

600kcmil

All 194℉ (90℃) copper wire, 40 lb-ft