Each cable is related to certain polarity.
During cable connection, make sure that the cable is connected to the proper location
DC Port for Negative ground system
DC Port for Positive ground system
IMPORTANT!
Please check if all cables are securely fastened and torqued.
Use copper conductors only.
Check that all conduit fittings are installed correctly.
Check that all fittings are sealed correctly if installed outdoors.
XP100U-H2/ XP100U-H4/ XP100U-H6
XP83U-H6
XP90U-H6
Number of strings
1, 2, 3 or 4 (1 fuse is standard and 2, 3, or 4 fuses are optional)
DC input voltage
300V ~ 600V
Maximum DC current
350A
290A
317A
XP100U-H2/ XP100U-H4/ XP83U-H6/ XP90U-H6/ XP100U-H6
Number of PV strings
Cable Size
Torque
Hot, Return
1
600kcmil
All 194℉ (90℃) copper wire, 40 lb-ft