Operating Manual KACO blueplanet 5.0TL3 - 9.0TL3

Status

Display

Explanation

Action

OS

79

Insulation meas-

urement

PV generator’s insulation is being

measured

-

-

FS

80

Insulation meas.

not possible

The insulation measurement cannot

be performed because the generator
voltage is too volatile.

-

-

FS

81,

82,
83

Protection shut-

down line volt.
L1 L2, L3

Overvoltage has been detected on

a conductor. An internal protective
mechanism has disconnected the
device to protect it against damage.

 In case of repeated

occurrence:
Notify your author-
ised electrician.

E

FS

84

Protection shut-

down undervolt.
DC link

A voltage deviation has been found

in the DC link. An internal protective
mechanism has disconnected the
device to protect it against damage.

 In case of repeated

occurrence:
Notify your author-
ised electrician.

E

FS

85

Protection shut-

down overvolt. DC
link

E

FS

87,

88,
89

Protection shut-

down overcurrent
L1, L2, L3

A current that has been found on a

conductor is too high. An internal
protective mechanism has discon-
nected the device to protect it against
damage.

 In case of repeated

occurrence:
Notify your author-
ised electrician.

E

FS

91,

92

Protect. shutdown

drop 2.5V

Protect. shutdown

drop 1.5V

Internal 2.5 V reference voltage out-

side of the permissible range.

Internal 1.5V reference voltage outside

of the permissible range.

 Notify your author-

ised electrician.

E

FS

97

Protection shut-

down overcurrent
HW

Too much power has been fed into the

grid. Complete disconnection of the
device.

 Notify authorised

electrician / KACO
Service

E/K

FS

100

Protect. shutdown

HW overheating

The device has been switched off

because the temperatures in the hous-
ing were too high.

 Check to make sure

that the fans are
working.

 Replace fan if nec-

essary.

B

E

FS

101

to
106

Temperature plau-

sibility error, effi

-

ciency, DC link, AFI
module, relay, DC/
DC converter

The unit has shut down because of

implausible internal measured values.

 Notify KACO Service

K

FS

108

up

to
113

Critical overvolt-

age/undervoltage
L1-L3

Grid voltage is outside of the upper

limits on the indicated phase.

 Notify your author-

ised electrician.

E

Table 4:

Operating status and fault messages on the display

10

Service

If you need help solving a technical problem with one of our KACO products, please contact our service hotline.

Please have the following information ready so that we can help you quickly and effi

ciently:

Device name / serial number

Date of installation / Start-up report

Fault message shown on the display / Description of the fault / Did you notice anything unusual? / What has
already been done to analyse the fault?