7 installation, 1 opening the connection area – KACO blueplanet 5.0 - 9.0 TL3 User Manual
Page 17

EN
Installation
Operating Manual KACO blueplanet 5.0TL3 - 9.0TL3
Page 17
Authorised electrician
7 Installation
DANGER
Lethal voltages are still present in the terminals and cables of the inverter even after the
inverter has been switched off and disconnected.
Severe injuries or death result if the cables and terminals in the inverter are touched.
The inverter must only be opened and installed by an accredited electrician, who has been approved
by the public power supplier (country-specifi c).
The inverter must be mounted in a fi xed position before being connected electrically.
›
Observe all safety regulations and current technical connection specifi cations of the responsible
power supply company.
›
Disconnect the AC and DC sides.
›
Secure both sides against being inadvertently switched back on.
›
Ensure that the AC and DC sides are completely isolated and voltage free.
›
Connect the inverter only after the aforementioned steps have been taken.
7.1
Opening the connection area
1
3
2
Figure 9: Uncover the DC connection
Key
1
Screwdriver
2
Cover to safeguard the DC connections
3
DC isolator switch
Opening the connection area
↻ You have mounted the inverter on the wall.
1.
Switch the DC isolator switches to 0 to remove the cover.
2. Carefully unlatch cover at the marked position using a screwdriver.
3. Remove cover and store for connection.
»
Make the electrical connection.