KACO blueplanet 5.0 - 9.0 TL3 User Manual
Page 51

EN
Maintenance/Troubleshooting
Operating Manual KACO blueplanet 5.0TL3 - 9.0TL3
Page 51
Status
Display
Explanation
Action
FS
41
42
Line failure:
Under voltage L1,
Over voltage L1,
The voltage of a grid phase is too low;
the grid cannot be fed into. The phase
experiencing failure is displayed.
Notify your author-
ised electrician.
E
43
44
Under voltage L2,
Over voltage L2,
45
46
Under voltage L3,
Over voltage L3,
FS
47
Grid failure: phase-
to-phase voltage
The measured line-to-line voltage is
outside of the tolerance limits.
FS
48
Line failure:
Underfrequency
Grid frequency is too low.
This fault may be grid-related.
Notify your author-
ised electrician.
E
FS
49
Line failure:
Overfrequency
Grid frequency is too high.
This fault may be grid-related.
Notify your author-
ised electrician.
E
FS
50
Line failure:
average voltage
The grid voltage measurement accord-
ing to EN 50160 has exceeded the
maximum permitted limit value.
This fault may be grid-related.
Notify your author-
ised electrician.
E
FS
56
Switch off via digi-
tal input
The inverter was disconnected from
the grid through a remote command.
Remote trip-off
Waiting for reconnection
FS
57
Waiting for
reconnect
Waiting time of the inverter after a
fault.
Inverter does not switch on
again until the country-specifi c
time has elapsed.
FS
58
Overtemperature
Control card
The temperature inside the unit was
too high. The inverter switches off to
prevent damage to the hardware.
Provide for suffi
cient
ventilation.
E
OS
60
Generator
voltage too high
The inverter does not begin feeding
into the grid until the PV voltage falls
below a specifi ed value.
-
-
OS
61
External
limit (%)
The external limit Power Control was activated by the primary system
controller. The inverter limits its power.
OS
63
Measured values
P(f )/frequency-dependent power reduction: Frequency-dependent
power reduction will be activated when the BDEW (German Association
of Energy and Water Industries) Medium Voltage Directive goes into
eff ect. Power reduction starts at a frequency of 50.2 Hz.
OS
64
Measured values
Output current limiting: The AC current is limited once the specifi ed
maximum value has been reached.
FS
70
Fan error
The fan is malfunctioning.
Replace
defective fan
E
FS
71
Fan error
The external fan is malfunctioning.
Replace
defective fan
E
FS
73
Standalone grid err.
Standalone mode was detected.
-
-
FS
78
Resid. current shut-
down (AFI)
Measured AFI fault current was > 180
mA.
Causes the device to switch off imme-
diately.
-
-
Table 4:
Operating status and fault messages on the display