EN

Maintenance/Troubleshooting

Operating Manual KACO blueplanet 5.0TL3 - 9.0TL3

Page 51

Status

Display

Explanation

Action

FS

41

42

Line failure:

Under voltage L1,

Over voltage L1,

The voltage of a grid phase is too low;

the grid cannot be fed into. The phase
experiencing failure is displayed.

 Notify your author-

ised electrician.

E

43

44

Under voltage L2,

Over voltage L2,

45

46

Under voltage L3,

Over voltage L3,

FS

47

Grid failure: phase-

to-phase voltage

The measured line-to-line voltage is

outside of the tolerance limits.

FS

48

Line failure:

Underfrequency

Grid frequency is too low.

This fault may be grid-related.

 Notify your author-

ised electrician.

E

FS

49

Line failure:

Overfrequency

Grid frequency is too high.

This fault may be grid-related.

 Notify your author-

ised electrician.

E

FS

50

Line failure:

average voltage

The grid voltage measurement accord-

ing to EN 50160 has exceeded the
maximum permitted limit value.
This fault may be grid-related.

 Notify your author-

ised electrician.

E

FS

56

Switch off via digi-

tal input

The inverter was disconnected from

the grid through a remote command.
Remote trip-off

 Waiting for reconnection

FS

57

Waiting for

reconnect

Waiting time of the inverter after a

fault.

Inverter does not switch on

again until the country-specifi c
time has elapsed.

FS

58

Overtemperature

Control card

The temperature inside the unit was

too high. The inverter switches off to
prevent damage to the hardware.

 Provide for suffi

cient

ventilation.

E

OS

60

Generator

voltage too high

The inverter does not begin feeding

into the grid until the PV voltage falls
below a specifi ed value.

-

-

OS

61

External

limit (%)

The external limit Power Control was activated by the primary system

controller. The inverter limits its power.

OS

63

Measured values

P(f )/frequency-dependent power reduction: Frequency-dependent

power reduction will be activated when the BDEW (German Association
of Energy and Water Industries) Medium Voltage Directive goes into
eff ect. Power reduction starts at a frequency of 50.2 Hz.

OS

64

Measured values

Output current limiting: The AC current is limited once the specifi ed

maximum value has been reached.

FS

70

Fan error

The fan is malfunctioning.

 Replace

defective fan

E

FS

71

Fan error

The external fan is malfunctioning.

 Replace

defective fan

E

FS

73

Standalone grid err.

Standalone mode was detected.

-

-

FS

78

Resid. current shut-

down (AFI)

Measured AFI fault current was > 180

mA.

Causes the device to switch off imme-

diately.

-

-

Table 4:

Operating status and fault messages on the display