Configuration and operation – KACO blueplanet 5.0 - 9.0 TL3 User Manual
Page 39

EN
Configuration and Operation
Operating Manual KACO blueplanet 5.0TL3 - 9.0TL3
Page 39
Coun-
try-spec.
setting
menu
level
Display/
setting
Action in this menu/meaning
0
1
2
3
1
Powador-protect
Confi gures the support for grid shutdown by a Powador
protect connected to the digital input of the inverter.
↻ For Auto/On: A Powador protect is operating in
the photovoltaic system and is connected to the
inverter at the digital input/output.
Auto: The inverter automatically detects a Pow-
ador-protect integrated into the photovoltaic
system.
On: The digital signal of the Powador protect must
be present to the digital input of the inverter for the
inverter to start with feed-in.
Off : The inverter does not check whether a Powador
protect is integrated in the photovoltaic system.
0
1
2
3
1
Iso.resistor
Set threshold value (in 1 kOhm steps) at which the
insulation monitor reports a fault.
DE, CH, BE,
FR, GB, IL, IT,
AT, PL, RU, ES,
KR, TH, ZA
0
1
2
3
1
Reactive power
Open the menu: Press the right arrow button or the
OK button.
Activating idle power process: select process and
press OK. The active process is highlighted.
0
1
2
3
2
cos-phi specifi ca-
tion
Confi gure power factor.
If a power factor is selected which is not equal to
1: Select the type of phase shift (under-excited/
over-excited).
DE, FR, GB, IL,
IT, AT, PL, RU,
ES, KR, TH,
UD, ZA
0
1
2
3
2
Q const.
Set the idle power Q (in %) to a fi xed value.
Select the type of phase shift (under-excited/
over-excited).
DE, CH, BE,
GB, IT, AT, PL
ES, KR, UD
0
1
2
3
2
cos-phi(P/Pn)
Open the menu: Press the right arrow button or the
OK button.
GB, IT, AT, ES,
KR
0
1
2
3
3
Lock-in voltage
Power range set as % of rated voltage, where the
network support process is active.
0
1
2
3
3
Lock-out
voltage
DE, BE, FR,
GB, IL, IT, AT,
PL, RU, ES,
KR, TH, UD
0
1
2
3
3
Number of
nodes
This option defi nes how many support points can be
defi ned in the subsequent menu. The maximum number
of confi gurable support points depends on the selected
grid type.
Specify the number of support points for the idle
power characteristic curve.
0
1
2
3
3
1., 2. ...Support
point
Specify the power factor for the 1st, 2nd (etc.) sup-
port point
If a power factor not equal to 0 is selected: Select the
type of phase shift (under-excited/over-excited).