KACO blueplanet 5.0 - 9.0 TL3 User Manual
Page 37

EN
Configuration and Operation
Operating Manual KACO blueplanet 5.0TL3 - 9.0TL3
Page 37
Coun-
try-spec.
setting
menu
level
Display/
setting
Action in this menu/meaning
0
1
2
3
1
Country
1.
Enter the four-digit password using the 4-way
button. The password is unit-specifi c.
2. Confi rm the entry with the OK button.
3. Set the desired country setting.
NOTE: This option infl uences the country-specifi c
operating settings of the inverter. Please consult KACO
service for further information.
DE, CH, FR,
GR, IT, GB
0
1
2
3
1
Grid type/guide-
line
Select the grid type for the inverter’s installation
location.
AU, BG, FR,
GR, PT, ES,
CZ, KR
0
1
2
3
1
Switch-off volt.
The inverter is equipped with redundant 3-phase moni-
toring. If the grid frequency exceeds or drops below the
confi gured values, the inverter switches off . The mini-
mum switch-off threshold can be set in 1 V increments.
Confi gure the switch-off values for undervoltage
and overvoltage.
Where necessary, set period from occurrence of the
fault to shutdown of the inverter.
DE, AU, BG,
FR, GR, HU,
IL, PT, ES, CZ,
KR
0
1
2
3
1
Switch-off freq.
The inverter continuously monitors the grid frequency. If
the grid frequency exceeds or drops below the confi g-
ured values, the inverter switches off .
Set limit values for underfrequency
and overfrequency in 0.1 Hz increments.
Set period from occurrence of the fault to shutdown
of the inverter.
DE, BE, FR,
IT, CH, AT, PL,
UD
0
1
2
3
1
Overvoltage shutd.
Activate or deactivate password protection.
Specify the shutdown threshold
for overvoltage shutdown.
The 10-minute average for the measured voltage as
per V VDE 0126-1-1:2006 is used.
Set period from occurrence of the fault to shutdown
of the inverter.
DE, FR, GB,
HU, IL, IN, IT,
AT, PL, RU, ES,
TH, ZA, UD
Specify the shutdown threshold
for fast and slow overvoltage shutdown.
Set period from occurrence of the fault to shutdown
of the inverter.
BG, FR, CZ,
UD
0
1
2
3
1
Voltage drop
The voltage drop between the inverter and the grid-
feed meter is added to the limit value that was set for
grid shutdown according to V VDE 0126-1-1:2006. The
limit value can be set from 0 to 11 V in 1 V increments.
Specify the switch-off value for the voltage drop (0
to 11 V).
DE, FR, GB,
HU, IL, IN, IT,
AT, PL, RU, ES,
TH, ZA, UD
0
1
2
3
1
Undervoltage
shutd.
Specify the shutdown threshold
for fast and slow undervoltage shutdown.
Set period from occurrence of the fault to shutdown
of the inverter.