Configuration and Operation

Operating Manual KACO blueplanet 5.0TL3 - 9.0TL3

Page 37

Coun-

try-spec.

setting

menu

level

Display/

setting

Action in this menu/meaning

0

1

2

3

1

Country

1.

Enter the four-digit password using the 4-way
button. The password is unit-specifi c.

2. Confi rm the entry with the OK button.

3. Set the desired country setting.

NOTE: This option infl uences the country-specifi c
operating settings of the inverter. Please consult KACO
service for further information.

DE, CH, FR,

GR, IT, GB

0

1

2

3

1

Grid type/guide-

line

 Select the grid type for the inverter’s installation

location.

AU, BG, FR,

GR, PT, ES,

CZ, KR

0

1

2

3

1

Switch-off volt.

The inverter is equipped with redundant 3-phase moni-

toring. If the grid frequency exceeds or drops below the
confi gured values, the inverter switches off . The mini-
mum switch-off threshold can be set in 1 V increments.

 Confi gure the switch-off values for undervoltage

and overvoltage.

 Where necessary, set period from occurrence of the

fault to shutdown of the inverter.

DE, AU, BG,

FR, GR, HU,

IL, PT, ES, CZ,

KR

0

1

2

3

1

Switch-off freq.

The inverter continuously monitors the grid frequency. If

the grid frequency exceeds or drops below the confi g-
ured values, the inverter switches off .

 Set limit values for underfrequency

and overfrequency in 0.1 Hz increments.

 Set period from occurrence of the fault to shutdown

of the inverter.

DE, BE, FR,

IT, CH, AT, PL,

UD

0

1

2

3

1

Overvoltage shutd.

 Activate or deactivate password protection.

 Specify the shutdown threshold

for overvoltage shutdown.
The 10-minute average for the measured voltage as
per V VDE 0126-1-1:2006 is used.

 Set period from occurrence of the fault to shutdown

of the inverter.

DE, FR, GB,

HU, IL, IN, IT,

AT, PL, RU, ES,

TH, ZA, UD

 Specify the shutdown threshold

for fast and slow overvoltage shutdown.

 Set period from occurrence of the fault to shutdown

of the inverter.

BG, FR, CZ,

UD

0

1

2

3

1

Voltage drop

The voltage drop between the inverter and the grid-

feed meter is added to the limit value that was set for
grid shutdown according to V VDE 0126-1-1:2006. The
limit value can be set from 0 to 11 V in 1 V increments.

 Specify the switch-off value for the voltage drop (0

to 11 V).

DE, FR, GB,

HU, IL, IN, IT,

AT, PL, RU, ES,

TH, ZA, UD

0

1

2

3

1

Undervoltage

shutd.

 Specify the shutdown threshold

for fast and slow undervoltage shutdown.

 Set period from occurrence of the fault to shutdown

of the inverter.