Configuration and operation – KACO blueplanet 5.0 - 9.0 TL3 User Manual
Page 38

EN
EN
Configuration and Operation
Page 38
Operating Manual KACO blueplanet 5.0TL3 - 9.0TL3
Coun-
try-spec.
setting
menu
level
Display/
setting
Action in this menu/meaning
DE, FR, GB,
IN, IT, AT, PL,
RU, ES, TH,
ZA, UD
0
1
2
3
1
Overfreq. shutd.
Set limit value for overfrequency shutdown.
0
1
2
3
1
Underfreq. shutd.
Set limit value for the underfrequency shutdown.
FR, IL, IN, IT,
AT, PL, RU,
TH, ZA, UD
0
1
2
3
1
Activation
condition
The inverter checks mains voltage and frequency. The
grid feed operation begins if the measured values are
within the set ranges.
Set minimum and maximum values for the switch-
ing on.
DE, CH, BE,
FR, GB, IL, IN,
IT, AT, PL, RU,
ES, TH, ZA,
UD
0
1
2
3
1
Connect time
Set period for grid observation (in seconds) when
switching on and reconnection after a fault.
IL, IT, ZA
0
1
2
3
1
P(f) Gradient
Set gradient of power limit function with increasing
frequency in % / Hz. This percentage relates to the
nominal frequency of 50 Hz
0
1
2
3
1
P(f) thresholds
Set the frequency thresholds for activating and
deactivating the power limitation in Hz.
0
1
2
3
1
DC connection
Select between automatic detection and manual
setting.
Note the connection examples! (See section 7.5.3 on
page 22)
0
1
2
3
1
DC starting volt.
The inverter begins feed-in as soon as this DC voltage is
present.
Set the starting voltage.
0
1
2
3
1
Const. volt. ctrl.
Lets you deactivate the MPP seek mode in order to oper-
ate the inverter with a constant DC voltage.
Activate or deactivate function.
Set value for constant voltage control (200 - 800 V).
NOTE: For voltages below the minimal MPP voltage the
possible input power is reduced. The input current is
limited here to 11A per input.
0
1
2
3
1
Power
limitation
The output power of the inverter can be set perma-
nently to a lower value than the maximum output
power by the internal power limiting. This may be nec-
essary in order to limit the maximum power rating of
the system at the grid connection point, upon the grid
operator's request.
The value can be protected from the very fi rst output
limitation entry. After setting a limitation, the value can
only be changed by entering a device-specifi c password.
1.
Activate password protection if necessary.
2. Specify the activation status.
3. Specify the limit value for maximum feed-in power.
4. Confi rm the entry with the OK button.