Installation

Operating Manual KACO blueplanet 5.0TL3 - 9.0TL3

Page 19

Authorised electrician

11. Secure the housing with a screwdriver (size 30).

Tighten the cable fi tting using a torque of 6.5 Nm.

»

Make the electrical connections.

NOTE

The permissible bending radius of at least 4 x the cable diameter should be observed during installa-
tion. Excessive bending force may negatively impact the protection rating.
All mechanical loads must be absorbed in front of the connection plug.

Recommended conductor cross-section

Protection

2,5 - 6,0 mm²

max. 25 A

Table 3:

Recommended conductor cross-section

Select conductor cross-section, safety type and safety value in accordance with the following master condi-
tions:

- Country specifi c installation standards

- Power rating of the device

- Line length

- Type of line installation

- Local temperatures

7.2.2

DC plug connector

5

1

2

6

4

3

1

2

15

4

3

7

Figure 16: Insert wires

Figure 17: Slide insert into sleeve

Figure 18: Check fastening

Key

1

Wires for DC connection

5

cable fi tting

2

Spring

6

Contact plug

3

Insert

7

Coupling

4

Sleeve

Confi guring the DC connector

↻ Connection area opened.
NOTE: Before proceeding with the isolation ensure that you don't cut any individual wires.

1.

Isolate wires for DC connection by 15 mm.

2. Insert isolated wires with twisted ends carefully up to the end stop.

NOTE: Wire ends must be visible in the spring.

3. Close the spring so that the spring latches.

4. Slide insert into sleeve.

5. Tighten cable fi tting with the help of a 15" fork wrench applying a torque of 2 Nm.

6. Join insert with contact plug.

7. Check latch by lightly pulling on the coupling.

»