Installation

Operating Manual KACO blueplanet 5.0TL3 - 9.0TL3

Page 27

Authorised electrician

NOTE

Use a suitable network cable of at least category 5. The maximum length of a network segment is
100 m. Ensure that the cable is correctly assigned. The Ethernet connection of the inverter supports
auto-sensing. You can use both crossed and 1:1 protectively-wired Ethernet connection cables.

Connecting an Ethernet cable to the inverter

1.

Loosen and remove the cover of the cable fi tting (see Figure 27 on page 25).

2. Remove the sealing insert.

3. Thread the connection cable through the cover of the cable fi tting and the sealing insert.

4. Insert the sealing insert into the cable fi tting.

5. Connect the connection cables to one of the corresponding Ethernet interfaces (see Figure 27 on page 25).

6. Attach and tighten the cover of the cable fi tting.

Connecting the inverter to the network

↻ Connect the Ethernet cable to the inverter.

↻ Confi gure the Ethernet interface in the confi guration menu.

 Connect the Ethernet cable to the network or a computer.

 Confi gure the Ethernet settings and the web server in the Settings/Network menu.

7.7.3

Connecting the fault signal relay

DANGER

Risk of fatal injury due to electric shock

Serious injury or death due to unintended use of the interface connections.

Ensure that for a connection, no grid voltage of insulated or just separated cables reaches SELF
areas.

Cap cables short enough that individual wires cannot come in contact with other cables or compo-
nents on the hard drive.

The contact is designed as an N/O contact and is labelled "Relay" on the circuit board.

Maximum contact load capacity DC: 30 V / 1 A. AC: 250 V / 1 A.

Connecting the fault signal relay

1.

Unscrew the cable fi tting.

2. Thread the connection cables through the cable fi tting.

3. Attach the connection cables to the connection terminals.

4. Tighten the cable fi tting.

7.7.4

Connecting "Inverter Off "

NOTE

The Powador-protect digital output can only be used with suitable KACO inverters. When using
devices from other manufacturers or in combination with KACO inverters, bus coupler circuit-break-
ers as a minimum must be used for shutting down devices from other manufacturers.