Maintenance/Troubleshooting

Page 44

Operating Manual KACO blueplanet 5.0TL3 - 9.0TL3

9.2

Cleaning the device

DANGER

Lethal voltages in the inverter

Serious injuries or death may occur if moisture gets into the inverter.

Only use completely dry objects to clean the inverter.

Only the exterior of the inverter should be cleaned.

Cleaning the device

 Do not use compressed air.

 Use a vacuum cleaner or a soft brush to remove dust from the fan cover, between the cooling fi ns and from

the top side of the inverter on a regular basis.

 Remove dust from the ventilation inlets if necessary.

 If necessary, remove the fan cover and remove deposits.

9.3

Shutting down for maintenance and troubleshooting

DANGER

Lethal voltages are still present in the terminals and cables of the inverter even after the
inverter has been switched off and disconnected.

Severe injuries or death result if the cables and terminals in the inverter are touched.

When there is solar radiation, DC voltage will be present at the open ends of the DC cables. Arcing
may occur if the DC cables are disconnected while they are still live.

The inverter is only permitted to be opened and serviced by an authorised, accredited electrician.

Observe all safety regulations and the current technical connection specifi cations from the relevant
power supply company.

Disconnect the AC and DC sides and secure against being inadvertently switched back on.

Do not touch the exposed ends of the cables.

Avoid short circuits.

Do not open the inverter until these two steps are complete.

After shutdown, wait at least 30 minutes before working on the inverter.

CAUTION

Destruction of the DC connection

The connection terminals can be destroyed by arcing if disconnected while still live.

It is absolutely essential that the shutdown sequence is carried out in the correct order.

Shutting down the inverter

1. Switch

off the grid voltage by turning off the external circuit breakers.

2. Disconnect the PV generator using the DC isolator switch.

DANGER! The DC cables are still live.

 Ensure that there is no voltage present on the grid connection terminals.

9.4

Replacing or cleaning the fans

The inverter is equipped with an axial fan. The axial fan this mounted on the left housing side.
Replace the fan:

In case of heavy soiling

If it is defective