Installation

Page 18

Operating Manual KACO blueplanet 5.0TL3 - 9.0TL3

Authorised electrician

7.2 Confi gure connections

7.2.1

AC connection plug

3

1

2

4

0,47 In

(12mm)

1,97 In

(50mm)

0,31 In

(8mm)

5

L3

L2

N

PE

L1

4

Figure 10: AC connection plug

Figure 11: Remove cable insulation

Figure 12: Connect cable to the con-

tact carrier

1 Nm

CLICK !

CLICK !

30

6,5 Nm

Figure 13: Tighten screws

Figure 14: Press contact carrier into the

housing

Figure 15: Tighten the cable screw

fi tting

Key

1

cable fi tting

4

Contact plug

2

Seal

5

Cable lengths

3

Housing

Confi gure AC connection plug

↻ Connection area opened.
1.

Slide the cable fi tting over the cable.

2. Select seal according to cable diameter used (8 ... 12 mm/ 12 ... 16 mm/ 16 ... 21 mm).

3. Slide the housing and seal over the cable.

4. Remove 50 mm of the outer cladding.

5. Shorten wires N, L1, L2, L3 by 8 mm.

6. Strip 12 mm of the insulation from wires (N, L1, L2, L3 , PE).

7. With

fl exible wires we recommend the use of wire sleeves conforming to DIN 46228 that are pressed together

using crimping pliers (CRIMPFOX 6).

8. Insert wires into the contacts in accordance with the markings on the contact carrier.

9. Tighten the screws on the contact carrier with 1 Nm.

10. Press contact carriers into the housing with an audible "click".