3 specifications – Yaskawa MP2000 Series I/O Module User Manual User Manual
Page 65

3.1 Outline of LIO-04/LIO-05 Modules
3.1.3 Specifications
65
3
LIO-04/LIO-05 Module
3.1.3 Specifications
The following shows the specifications of the LIO-04/LIO-05 Modules.
( 1 ) Hardware Specifications
( 2 ) Environmental Conditions
Item
Specifications
Classification
I/O Module
Name
LIO-04
LIO-05
Model
JAPMC-IO2303
JAPMC-IO2304
Digital Input
32 inputs
24 VDC
±
20% (+19.2V to +28.8V), 4.1 mA (TYP),
combined sink mode/source mode inputs (DI-00, -01, -16, and -17 also used for interrupts)
Number of simultaneously ON inputs: 16 (8/connector with 24 VDC),
10 (5/connector with 28.8 VDC)
*For details, refer to ( 3 ).
Digital Output
32 outputs
24 VDC
±
20% (+19.2V to +28.8V),
100 mA max.,
transistor outputs, sink mode outputs
32 outputs
24 VDC
±
20% (+19.2V to +28.8V),
100 mA max.,
transistor outputs, source mode outputs
LED Indicators
RUN (green)
FUSE (red)
Connectors
CN1: I/O connector
CN2: I/O connector
Current Consumption
500mA max.
Dimensions (mm)
125
× 95 (H× D)
Mass
80 g
Item
Specifications
Environmental
Conditions
Ambient Operating
Temperature
0 to 55
°C
Ambient Storage
Temperature
-25 to 85
°C
Ambient Operating
Humidity
30% to 95% (with no condensation)
Ambient Storage Humidity
5% to 95% (with no condensation)
Pollution Level
Pollution level 1 (conforming to JIS B 3501)
Corrosive Gas
There must be no combustible or corrosive gas.
Operating Altitude
2,000 m above sea level or lower
Mechanical
Operating
Conditions
Vibration Resistance
Conforming to JIS B 3502:
• 10 to 57 Hz with single-amplitude of 0.075 mm
• 57 to 150 Hz with fixed acceleration of 9.8 m/s
2
• 10 sweeps each in X, Y, and Z directions
(sweep time: 1 octave/min)
Shock Resistance
Conforming to JIS B 3502:
Peak acceleration of 147 m/s
2
twice for 11 ms each in the X, Y, and Z direc-
tions
Electrical
Operating
Conditions
Noise Resistance
Conforming to EN 61000-6-2, EN 55011 (Group 1, Class A)
Power supply noise (FT noise): 2 kV min., for one minute
Radiation noise (FT noise): 1 kV min., for one minute
Ground noise (impulse noise): 1 kV min., for 10 minutes
Electrostatic noise (contact discharge): 4 kVmin., for 10 times
Installation
Requirements
Ground
Ground to 100
Ω max.
Cooling Method
Natural cooling