5.1 Outline of DO-01 Module
5.1.4 LED Indicators
124
( 2 ) Environmental Conditions
5.1.4 LED Indicators
The following table shows the DO-01 Module status when each indicator lamp is lit or unlit.
Item
Specifications
Environmental
Conditions
Ambient Operating
Temperature
0
to 55°C
Ambient Storage
Temperature
-25
to 85°C
Ambient Operating
Humidity
30% to 95% (with no condensation)
Ambient Storage
Humidity
5% to 95% (with no condensation)
Pollution Level
Pollution level 1 (conforming to JIS B 3501)
Corrosive Gas
There must be no combustible or corrosive gas.
Operating Altitude
2,000 m above sea level or lower
Mechanical
Operating
Conditions
Vibration Resistance
Conforming to JIS B 3502:
• 10 to 57 Hz with single-amplitude of 0.075 mm
• 57 to 150 Hz with fixed acceleration of 9.8 m/s
2
• 10 sweeps each in X, Y, and Z directions
(sweep time: 1 octave/min)
Shock Resistance
Conforming to JIS B 3502:
Peak acceleration of 147 m/s
2
twice for 11 ms each in the X, Y, and Z direc-
tions
Electrical
Operating
Conditions
Noise Resistance
Conforming to EN 61000-6-2, EN 55011 (Group 1, Class A)
Power supply noise (FT noise): 2 kV min., for one minute
Radiation noise (FT noise): 1 kV min., for one minute
Ground noise (impulse noise): 1 kV min., for 10 minutes
Electrostatic noise (contact discharge): 4 kV min., for 10 times
Installation
Requirements
Ground
Ground to 100
Ω max.
Cooling Method
Natural cooling
Indicator
Color
When Lit
When Unlit
RUN
Green
Normal operation
Error occurrence
FUSE
Red
One or some of the output protection
fuses is blown out.
Output protection fuses are normal.
FUSE