Yaskawa command class – Yaskawa DeviceNet Option Card CM05x User Manual
Page 77

DeviceNet Object Paths A-12
Yaskawa Command Class
DeviceNet
Path
DeviceNet
Services
DeviceNet
Data Type
# of
Bytes
Description
Notes
100 / 0 / 1
GET
uint
2
Yaskawa Object Revision
The DeviceNet specification revision of the Yaskawa Object.
100 / 0 / 2
GET
uint
2
Max Instance in this Class
1
100 / 0 / 6
uint
2
Max Class Attribute Number
The number of the last Class Attribute Implemented
100 / 0 / 7
uint
2
Max Instance Attribute Number
The number of the last Instance Attribute Implemented
100 / 1 / 1
GET/SET
uint
2
Operation Command
Bit
0
Forward Run/Stop
Bit
1
Reverse Run/Stop
Bit
2
Terminal S3 Function
Bit
3
Terminal S4 Function
Bit
4
Terminal S5 Function
Bit
5
Terminal S6 Function
Bit
6
Terminal S7 Function
Bit
7
Terminal S8 Function (F7 and G7 only)
Bit
8
External Fault
Bit
9
Fault Reset
100 / 1 / 2
GET/SET
uint
2
Frequency Reference
0.01 Hz
100 / 1 / 3
GET/SET
uint
2
Torque Reference
0.1 % Flux Vector mode only (F7 and G7 only)
100 / 1 / 4
GET/SET
uint
2
Torque Compensation
0.1 % Flux Vector mode only (F7 and G7 only)
100 / 1 / 5
Reserved for Future Use
100 / 1 / 6
GET/SET
uint
2
Analog Output FM Setting
Terminal FM -10V/-660 ~ +10V/+660
100 / 1 / 7
GET/SET
uint
2
Analog Output AM Setting
Terminal AM -10V/-660 ~ +10V/+660
100 / 1 / 8
GET/SET
uint
2
Digital Output Setting
Bit
0
Close Multi-function Output Terminal M1-M2
Bit
1
Close Multi-function Output Terminal M3-M4
Bit
2
Close Multi-function Output Terminal M5-M6
(F7 and G7 only)
Bit
3
Not Used
Bit
4
Not Used
Bit
5
Not Used
Bit
6
Enable Fault Contact
Bit
7
Close Fault Contact (effective only when bit 6 = 1)
The DeviceNet Path is given in the format: Class ID / Instance ID / Attribute ID.
Attributes shown in GREY are not supported by the DRIVE DeviceNet Option Board.
Drive products may provide additional inputs and outputs than are supported through DeviceNet.
Example: G7 models have 12 digital inputs and 8 digital inputs are supported through DeviceNet.