beautypg.com

Motor class – Yaskawa DeviceNet Option Card CM05x User Manual

Page 72

background image


DeviceNet Object Paths A-7

Motor Class

DeviceNet

Path

DeviceNet

Services

DeviceNet
Data Type

# of

Bytes

Description

Notes

40 / 0 / 1

GET

uint

2

Motor Object Revision

The DeviceNet specification revision of the Motor Object.

40 / 0 / 6

-

uint

2

Max Class Attribute Number

The number of the last Class Attribute Implemented.

40 / 0 / 7

-

uint

2

Max Instance Attribute Number

The number of the last Instance Attribute Implemented.

40 / 1 / 1

GET

usint

1

Number of Motor Attributes Supported

7

40 / 1 / 2

-

array

-

Motor Attribute List

-

40 / 1 / 3

GET/SET

usint

1

Motor Type

0

Non-standard motor

1

PM DC Motor

2

FC DC Motor

3

PM Synchronous Motor

4

FC synchronous Motor

5

Switched Reluctance Motor

6

Wound Rotor Induction Motor (default)

7

Squirrel Cage Induction Motor

8

Stepper Motor

9

Sinusoidal PM BL Motor

10

Trapezoidal PM BL Motor

40 / 1 / 4

-

string

-

Motor Catalog Number

Motor Manufacturer’s Catalog Number.

40 / 1 / 5

-

string

-

Motor Manufacturer

Motor Manufacturer’s Name.

40 / 1 / 6

GET/SET

uint

2

Motor Rated Current

Units: 0.1 Amps NOTE: This setting is not the same as
Drive parameter E2-01 (Path 107 / 1 / 15).
The setting of 40 / 1 / 6 does not effect Drive operation
(Drive model dependent default).

40 / 1 / 7

GET/SET

uint

2

Motor Rated Voltage

Units: Volts (230 or 460 Volts default)

40 / 1 / 8

-

udint

4

Motor Rated Power

Units: Watts

40 / 1 / 9

GET/SET

uint

2

Motor Rated Frequency

Units: Hz (60 Hz default)

40 / 1 / 10

-

uint

2

Motor Rated Temperature

Units: degrees C

40 / 1 / 11

GET/SET

uint

2

Motor Maximum Speed

Units: RPM (1800 RPM default)

40 / 1 / 12

-

uint

2

Motor Pole Count

Number of poles of the motor

40 / 1 / 13

-

udint

4

Motor Torque Constant

Units: 0.001 X Nm/A

40 / 1 / 14

-

udint

4

Motor Rotor Inertia

Units: 10

-6

X kg m

2

40 / 1 / 15

GET/SET

uint

2

Motor Base Speed

Units: RPM (1750 RPM default)

40 / 1 / 19

-

usint

1

Service Factor

Units: %

The Motor Class is required for compliance with the AC Drive Profile. Instance 1, Attributes 3, 6 and 7 are required. All other attributes are

optional.

The DeviceNet Path is given in the format: Class ID / Instance ID / Attribute ID.
Attributes shown in GREY are not supported by the Drive DeviceNet Option Board.