beautypg.com

Yaskawa AC Drive Z1000 User Manual

Page 364

background image

2.

Place the drive and EMC noise filter in the same enclosure.

3.

Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.

4.

Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.

A

B

D

E

C

M

U/T1

V/T2

W/T3

U

V

W

A – Drive
B – 10 m max. cable length between

drive and motor

C – Motor

D – Metal conduit
E – Ground wire should be as short as

possible.

Figure D.2 Installation Method

5.

Make sure the protective earthing conductor complies with technical standards and local safety regulations.

C

B

A

A – Braided shield cable
B – Metal panel

C – Cable clamp (conductive)

Figure D.3 Ground Area

D.2 European Standards

364