For an example custom v/f – Yaskawa AC Drive Z1000 User Manual
Page 135

Output Voltage (V)
Frequency (Hz)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
Figure 4.22 V/f Pattern
Note:
1. The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
2. To make the V/f pattern a straight line below E1-06, set E1-09 equal to E1-07. In this case the E1-08 setting is disregarded.
3. E1-03 is unaffected when the drive is initialized, but E1-04 through E1-13 return to their default values.
4. Only use E1-11, E1-12, and E1-13 to fine-tune the V/f pattern in the constant output range. These parameters rarely need to be changed.
n
E2-01: Motor Rated Current
Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on
the motor nameplate.
No.
Parameter Name
Setting Range
Default
E2-01
Motor Rated Current
10% to 200% of the drive
rated current
Determined by
o2-04
Note:
1. The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the
drive is set for a maximum applicable motor capacity up to and including 11 kW, 2A0031, 4A0021 (input voltage of 460 V or higher)
or 4A0027 (input voltage of lower than 460 V) and one decimal place (0.1 A) if the maximum applicable motor capacity is higher than
11 kW, 2A0046, 4A0027 (input voltage 460 V or higher) or 4A0034 (input voltage lower than 460 V).
2. An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly
to prevent this error.
n
E2-11: Motor Rated Power
Sets the motor rated power in kW. If Auto-Tuning completes successfully, the value entered to T1-02 will automatically be
saved to E2-11.
No.
Parameter Name
Setting Range
Default
E2-11
Motor Rated Power
0.00 to 370.00 kW
Determined by
o2-04
n
E5-02: Motor Rated Power
Sets the rated power of the motor. Determined by the value set to T2-04 during Stationary Auto-Tuning for PM motors.
No.
Parameter Name
Setting Range
Default
E5-02
Motor Rated Power
0.10 to 370.00 kW
Determined by
o2-04
n
E5-03: Motor Rated Current
Sets the motor rated current in amps. Automatically set when the value is entered to T2-06 during Auto-Tuning.
No.
Parameter Name
Setting Range
Default
E5-03
Motor Rated Current
10 to 200% of drive rated
current
Determined by
o2-04
Note:
The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the drive
is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable motor
capacity is higher than 11 kW.
4.7 Basic Drive Setup Adjustments
YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual
135