U6: operation status monitors – Yaskawa AC Drive Z1000 User Manual
Page 335

No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U5-06
(7D3)
PI Adjusted Feedback
PID Diff Fdbk
Displays the difference of both feedback values if differential
feedback is used (U5-01 - U5-05).
If differential feedback is not used, then U5-01 and U5-06 will
be the same.
10 V: 100%
0.01%
U5-07
(72)
AUTO Mode Frequency
Reference Value
AUTO mode Fref
Displays the Frequency reference value at AUTO Mode.
No signal output
available
0.01 Hz
U5-08
(73)
HAND Mode Frequency
Reference Value
HAND mode Fref
Displays the Frequency reference value at HAND Mode.
No signal output
available
0.01 Hz
U5-14
(86B)
PI Output Upper 4 Digits PI Output U4
Displays Custom PI output. U5-14 shows the upper 4 digits.
10V: (b5-43 x
10000) + b5-44
<1>
1
U5-15
(86C)
PI Output Lower 4 Digits PI Output L4
Displays Custom PI output. U5-15 shows the lower 4 digits.
No signal output
available
0.01
U5-17
(302A) PI2 Setpoint
PI2 Set-point
Displays the secondary PI setpoint.
10 V: Max
frequency
0.01%
U5-18
(302B) PI2 Feedback
PI2 Feedback
Displays the secondary PI feedback value.
10 V: Max
frequency
0.01%
U5-19
(302C) PI2 Input
PI2 Input
Displays the secondary PI input (deviation between PI target and
feedback).
10 V: Max
frequency
0.01%
U5-20
(302D) PI2 Output
PI2 Output
Displays the secondary PI control output.
10 V: Max
frequency
0.01%
U5-30
(3000)
Time Hr Min HHMM
Time Hr Min HHMM Displays the current time (Hours and Minutes).
No signal output
available
1
U5-31
(3001)
Date Year
Date Year
Displays the current year.
No signal output
available
1
U5-32
(3002)
Date Mo Day MMDD
Date Mo Day MMDD Displays the current date (Month and Day).
No signal output
available
1
U5-33
(3003)
Day of the Week
Date Week
0: Sun
1: Mon
2: Tues
3: Wed
4: Thur
5: Fri
6: Sat
Displays the current day of the week.
0: Sunday
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
No signal output
available
1
<1> Analog Output selection text is: “PI Output 2”.
u
U6: Operation Status Monitors
No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U6-01
(51)
Motor Secondary
Current (Iq)
Mot SEC Current
Displays the value of the motor secondary current (Iq). Motor
rated secondary current is 100%.
10 V: Motor
secondary rated
current
0.1%
U6-02
(52)
Motor Excitation
Current (Id)
Mot EXC Current
OLV/PM
OLV/PM
Displays the value calculated for the motor excitation current (Id).
Motor rated secondary current is 100%.
10 V: Motor
secondary rated
current
0.1%
U6-05
(59)
Output Voltage
Reference (Vq)
Voltage Ref (Vq)
OLV/PM
OLV/PM
Output voltage reference (Vq) for the q-Axis.
10 V: 200 Vrms
<1>
0.1 Vac
U6-06
(5A)
Output Voltage
Reference (Vd)
Voltage Ref (Vd)
OLV/PM
OLV/PM
Output voltage reference (Vd) for the d-Axis.
10 V: 200 Vrms
<1>
0.1 Vac
U6-21
(7D5)
Offset Frequency
Offset Frequency
Displays the frequency added to the main frequency reference.
–
0.1%
U6-80 to
U6-99
(7B0 to
7F9)
Option Monitors 1 to
20
–
Output monitor for option card.
Refer to Option Instruction manual for details
No signal output
available.
–
<1> Values shown are specific to 200 V class drives. Double the values for 400 V class drives.
B.13 U: Monitors
YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual
335
B
Parameter List