Page 181

background image

Setting 2: Fast Stop

If an overheat alarm occurs, the drive decelerates to stop using the Fast Stop time (C1-09). If a digital output is programmed

for “fault” (H2-oo = E), this output will be triggered.

Setting 3: Alarm Only

If an overheat alarm occurs, an alarm is output and the drive continues operation.

Setting 4: Operation with Reduced Speed

If an overheat alarm occurs, the operation continues with the speed reduced to the level set to parameter L8-19. If the oH alarm

is still present after 10 s, the speed is reduced again. The amount of speed reduction depends on how often the alarm repeats.

If the oH alarm disappears while the drive is operating at a reduced speed, the drive will switch to the previous speed in 10 s

increments until reaching base frequency.

Figure 4.36

explains the operation with reduced speed during an oH alarm. A digital

output programmed for 4D is switched when the oH alarm is still active after ten reduction cycles.

10 s

etc.

time

10 s

10 s

10 s

10 s

10 s

10 s

f

ref

× (L8-19)

f

ref

× (L8-19)

2

f

ref

× (L8-19)

4

f

ref

× (L8-19)

3

f

ref

Output frequency

Reset oH

Alarm

Reset oH

Alarm

Digital ouput (4D)

oH

Alarm

oH

Alarm

oH

Alarm

oH

Alarm

oH alarm number

Figure 4.36 Output Frequency Reduction During Overheat Alarm

n

L8-05: Input Phase Loss Protection Selection

Enables or disables the input phase loss detection.

No.

Name

Setting Range

Default

L8-05

Input Phase Loss Protection Selection

0, 1

1

Setting 0: Disabled
Setting 1: Enabled

Enables input phase loss detection. Since measuring the DC bus ripple detects input phase loss, a power supply voltage

imbalance or main circuit capacitor deterioration may also trigger a phase loss fault (PF).
Detection is disabled if:
• The drive is decelerating.
• No Run command is active.
• Output current is less than or equal to 30% of the drive rated current.

n

L8-06: Input Phase Loss Detection Level

Sets the Input Phase Loss Detection (PF) Level.
Triggers PF fault when there is an imbalance larger than the value set to L8-06 in the drive input power voltage.
Detection Level = 100% = Voltage Class ×

4.13 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

181

4

Start-Up Programming & Operation