Changing parameter settings or values, Drive mode details, Programming mode details – Yaskawa AC Drive Z1000 User Manual
Page 115

n
Drive Mode Details
The following actions are possible in the Drive Mode:
• Run and stop the drive
• Monitor the operation status of the drive (frequency reference, output frequency, output current, output voltage, etc.)
• View information on an alarm
• View a history of alarms that have occurred
n
Programming Mode Details
The following actions are possible in the Programming Mode:
• Parameter Setting Mode: Access and edit all parameter settings.
• Verify Menu: View a list of parameters that have been changed from the default values.
• Setup Group: Access a list of commonly used parameters to simplify setup (
Refer to Simplified Setup Using the Setup
).
• Auto-Tuning Mode: Automatically calculate and set motor parameters to optimize drive performance.
u
Changing Parameter Settings or Values
This example explains changing C1-02 (Deceleration Time 1) from 30.0 seconds (default) to 20.0 seconds.
Step
Display/Result
1. Turn on the power to the drive. The initial display appears.
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00 A
DRV
Freq Ref (AI)
Rdy
FWD
LSEQ
LREF
2. Press
or
until the Parameter Setting Mode screen appears.
HELP
- MODE -
PRG
DATA
Programming
FWD
3. Press
to enter the parameter menu tree.
-PRMSET-
Initialization
Select Language
PRG
A
1-00= 0
←
→
FWD
4. Press
or
to select the C parameter group.
←
→
-PRMSET-
Basic Setup
Accel Time 1
PRG
C
1-01=
30.0 sec
←
→
FWD
5. Press
two times.
-PRMSET-
Accel/Decel
Accel Time 1
PRG
C
1
-01=
30.0 sec
-PRMSET-
C1-
01
= 30.0Sec
(0.0~6000.0)
“30.0 sec”
PRG
Accel Time 1
←
→
FWD
←
→
FWD
6. Press
or
to select parameter C1-02.
-PRMSET-
C1-
02
= 30.0Sec
(0.0~6000.0)
“30.0 sec”
PRG
Decel Time 1
←
→
FWD
7. Press
to view the current setting value (10.0 s). The leftmost digit flashes.
-PRMSET-
C1-02=
0
030.0Sec
(0.0~6000.0)
“30.0 sec”
PRG
Decel Time 1
←
→
FWD
8. Press
F1
,
F2
, or
until the desired number is selected. “1” flashes.
-PRMSET-
C1-02=00
3
0.0Sec
(0.0~6000.0)
“30.0 sec”
PRG
Decel Time 1
←
→
FWD
4.3 The Drive, Programming, and Clock Adjustment Modes
YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual
115
4
Start-Up Programming & Operation