H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function
LCD Display
Description
Page
20
Drive overheat pre-
alarm (oH)
OH Prealarm
Closed: Heatsink temperature exceeds the parameter L8-02 value.
–
2F
Maintenance period
Maintenance
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay
may require maintenance.
–
37
During frequency output During RUN 2
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial
Excitation is being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is
not being performed).
–
38
Drive enabled
Drive Enable
Closed: Multi-function input set for “Drive enable” is closed (H1-oo = 6A)
–
39
Watt hour pulse output Watt-hour Pulse
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate
the kWh count.
–
3A
Drive overheat alarm
OH Alarm 2
Closed: An external device triggered an overheat warning in the drive.
–
3D
During speed search
During SpdSrch
Closed: Speed Search is being executed.
–
3E
PI feedback low
PID Feedback Low
Closed: PI feedback level is too low.
–
3F
PI feedback high
PID FeedbackHigh
Closed: The PI feedback level is too high.
–
4A
During KEB Ride-Thru During KEB
Closed: KEB Ride-Thru is being performed.
–
4B
During short circuit
braking
During SC Brake
OLV/PM
OLV/PM
Closed: Short Circuit Braking is active.
–
4C
During fast stop
During Fast Stop
Closed: A Fast Stop command has been entered from the operator or input
terminals.
–
4D
oH Pre-alarm time limit OH Pre-Alarm
Closed: oH pre-alarm time limit has passed.
–
50
Waiting for run
Waiting for Run
Closed: Delay executing any run command until the time set to b1-11 has expired.
–
51
Sequence timer 1 active SeqTimer Disable
Closed: Sequence timer 1 is active.
–
52
Sequence timer 2 active SeqTimer Cancel
Closed: Sequence timer 2 is active.
–
53
Sequence timer 3 active Sequence timer 3
Closed: Sequence timer 3 is active.
–
54
Sequence timer 4 active Sequence Timer 4
Closed: Sequence timer 4 is active.
–
58
Underload detection
UL6
Closed: Underload is detected.
–
60
Internal cooling fan
alarm
Fan Alrm Det
Closed: Internal cooling fan alarm
–
71
Secondary PI Feedback
Low
PI2 Feedback Low
Closed: PI2 feedback level is too low.
–
72
Secondary PI Feedback
High
PI2 FeedbackHigh
Closed: The PI2 feedback level is too high.
–
A4
BP Drive Relay Contact BP Emg Override
Closed: Line voltage is being supplied to the drive, and the motor is being run via
the drive.
–
A5
BP Bypass Relay
Contact
BP Drv/Bypss Sel
Closed: Line voltage is being supplied directly to the motor.
–
A6
BP BAS Interlock Relay
Contact
BP BAS Interlock
Closed: Actuation signal for options dampers.
–
A9
Relay Operator Control PI2 Disable N.C.
Closed: F1 (F2) key toggle relay output.
–
B2
BAS Interlock Relay
Contact
BAS Interlock
A Run command is active or voltage is output. Actuation signal for damper.
–
100 to
1B2
Function 0 to b2 with
inverse output
Note: A prefix of "!" is
added to represent
inverse functions on the
LCD keypad display.
Example: “!Zero speed”
–
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1oo to reverse the output signal of that specific function.
–
B.7 H Parameters: Multi-Function Terminals
YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual
305