b5-40
Frequency Reference Monitor Content During PI
0, 1
0
Setting 0: Frequency Reference after PI
Monitor U1-01 displays the frequency reference increased or reduced for the PI output.
Setting 1: Frequency Reference
Monitor U1-01 displays the frequency reference value.
n
b5-41: PI Unit Selection
Sets the display units in U5-14 and U5-15.
No.
Name
Setting Range
Default
b5-41
PI Unit Selection
0 to 14
0
Setting 0: WC (Inch of Water)
Setting 1: PSI (Pounds per Square Inch)
Setting 2: GPM (Gallons per Minute)
Setting 3: F (Degrees Fahrenheit)
Setting 4: CFM (Cubic Feet per Minute)
Setting 5: CMH (Cubic Meters per Hour)
Setting 6: LPH (Liters per Hour)
Setting 7: LPS (Liters per Second)
Setting 8: Bar (Bar)
Setting 9: Pa (Pascal)
Setting 10: C (Degrees Celsius)
Setting 11: Mtr (Meters)
Setting 12: Ft (Feet)
Setting 13: LPM (Liters per Minute)
Setting 14: CMM (Cubic Meters per Minute)
n
b5-42: PI Output Monitor Calculation Method
No.
Name
Setting Range
Default
b5-42
PI Output Monitor Calculation Method
0 to 3
0
Setting 0: Linear
The monitor displays PI output.
Setting 1: Square Root
The monitor displays square root PI output.
Setting 2: Quadratic
The monitor displays 1/(PI output)
2
Setting 3: Cubic
The monitor displays 1/(PI output)
3
n
b5-43/b5-44: Custom PI Output Monitor Setting 1/2
Set the maximum monitor value at maximum frequency. U5-14 and U5-15 show Custom PI output. U5-14 shows the upper
4 digits and U5-15 shows the lower 4 digits. It shows 999999.99 maximum.
No.
Name
Setting Range
Default
b5-43
Custom PI Output Monitor Setting 2
0 to 9999
0
b5-44
Custom PI Output Monitor Setting 2
0.00 to 99.99
0.00