Yaskawa AC Drive Z1000 User Manual
Page 285

No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
b5-04
(1A8)
Integral Limit Setting
PID I Limit
Sets the maximum output possible from the integrator as a
percentage of the maximum output frequency.
Default: 100.0%
Min.: 0.0
Max.: 100.0
b5-06
(1AA)
PI Output Limit
PID Limit
Sets the maximum output possible from the entire PI controller
as a percentage of the maximum output frequency.
Default: 100.0%
Min.: 0.0
Max.: 100.0
b5-07
(1AB)
PI Offset Adjustment
PID Offset
Applies an offset to the PI controller output. Set as a percentage
of the maximum output frequency.
Default: 0.0%
Min.: -100.0
Max.: 100.0
b5-08
(1AC)
PI Primary Delay Time
Constant
PID Delay Time
Sets a low pass filter time constant on the output of the PI
controller.
Default: 0.00 s
Min.: 0.00
Max.: 10.00
b5-09
(1AD)
PI Output Level
Selection
Output Level Sel
0: Normal Character
1: Rev Character
0: Normal output (direct acting)
1: Reverse output (reverse acting)
Default: 0
Range: 0, 1
b5-10
(1AE)
PI Output Gain Setting Output Gain
Sets the gain applied to the PI output.
Default: 1.00
Min.: 0.00
Max.: 25.00
b5-11
(1AF)
PI Output Reverse
Selection
Output Rev Sel
0: 0 limit
1: Reverse
0: Negative PI output triggers zero limit.
1: Rotation direction reverses with negative PI output.
Note:
When using setting 1, make sure reverse
operation is permitted by b1-04.
Default: 0
Range: 0, 1
b5-12
(1B0)
PI Feedback Loss
Detection Selection
Fb loss Det Sel
0: DO Only - Always
1: Alarm - Always
2: Fault - Always
3: DO Only@PID
Enbl
4: Alarm @ PID Enbl
5: Fault @ PID Enbl
0: Digital Output Only
(Remains active when PI is disabled by digital input)
1: Alarm output, drive continues operation (Remains active
when PI is disabled by digital input)
2: Fault output, drive output is shut off (Remains active when
PI is disabled by digital input)
3: Digital output only. No detection when PI is disabled by
digital input.
4: Alarm detection. No detection when PI is disabled by digital
input.
5: Fault detection. No detection when PI is disabled by digital
input.
Default: 0
Range: 0 to 5
b5-13
(1B1)
PI Feedback Loss
Detection Level
Fb loss Det Lvl
Sets the PI feedback loss detection level as a percentage of the
maximum output frequency.
Default: 0%
Min.: 0
Max.: 100
b5-14
(1B2)
PI Feedback Loss
Detection Time
Fb loss Det Time
Sets a delay time for PI feedback loss.
Default: 1.0 s
Min.: 0.0
Max.: 25.5
b5-15
(1B3)
PI Sleep Function Start
Level
PID Sleep Level
Sets the frequency level that triggers the sleep/snooze function. Default:
<1>
Min.: 0.0 Hz
Max.: 240.0 Hz
b5-16
(1B4)
PI Sleep Delay Time
PID Sleep Time
Sets a delay time before the sleep/snooze function is triggered. Default: 0.0 s
Min.: 0.0
Max.: 25.5
b5-17
(1B5)
PI Accel/Decel Time
PID Acc/Dec Time
Sets the acceleration and deceleration time to PI setpoint.
Default: 0.0 s
Min.: 0.0
Max.: 6000.0
b5-18
(1DC)
PI Setpoint Selection
PID Setpoint Sel
0: Disabled
1: Enabled
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
b5-19
(1DD)
PI Setpoint Value
PID Setpoint
Sets the PI target value when b5-18 = 1. Set as a percentage of
the maximum output frequency.
Default: 0.00%
Min.: 0.00
Max.: 600.00
<2>
b5-20
(1E2)
PI Setpoint Scaling
PID Disp Scaling
0: 0.01Hz units
1: 0.01% units
2: r/min
3: User Units
0: 0.01 Hz units
1: 0.01% units (100% = max output frequency)
2: r/min (number of motor poles must entered)
3: User-set (set scaling to b5-38 and b5-39)
Default: 1
Range: 0 to 3
B.2 b: Application
YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual
285
B
Parameter List