Table 4.25 Predefined V/f Patterns
Setting
Specification
Characteristic
Application
0
50 Hz
Constant torque
For general purpose applications. Torque remains constant
regardless of changes to speed.
1
60 Hz
2
60 Hz (with 50 Hz base)
3
72 Hz (with 60 Hz base)
4
50 Hz, Variable torque 1
Variable torque
For fans, pumps, and other applications where the required
torque changes as a function of the speed.
5
50 Hz, Variable torque 2
6
50 Hz, Variable torque 3
7
50 Hz, Variable torque 4
8
50 Hz, Mid starting torque
High starting torque
Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.
9
50 Hz, High starting torque
A
60 Hz, Mid starting torque
B
60 Hz, High starting torque
C
90 Hz (with 60 Hz base)
Constant output
Output voltage is constant when operating at greater than
60 Hz.
D
120 Hz (with 60 Hz base)
E
180 Hz (with 60 Hz base)
F
<1>
60 Hz
Variable torque
Used for variable torque applications. The default setting is
the same as V/f pattern Setting 7.
<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04
to E1-13 are equal to predefined V/f pattern 1.
The following tables show details on predefined V/f patterns.
Predefined V/f Patterns for Models 2A0011 to 2A0017 and 4A0005 to 4A0011
The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives.
Table 4.26 Constant Torque Characteristics, Settings 0 to 3
Setting = 0
50 Hz
Setting = 1
60 Hz
Setting = 2
60 Hz
Setting = 3
72 Hz
0
10.4
230
1.3 2.5
50
17.3
V
oltage (V)
Frequency (Hz)
0
10.4
17.3
230
1.5 3
60
V
oltage (V)
Frequency (Hz)
0
10.4
17.3
230
1.5 3
60
50
V
oltage (V)
Frequency (Hz)
0
10.4
17.3
230
1.5 3
72
60
V
oltage (V)
Frequency (Hz)
Table 4.27 Variable Torque Characteristics, Settings 4 to 7
Setting = 4
50 Hz
Setting = 5
50 Hz
Setting = 6
60 Hz
Setting = 7
60 Hz
0
9.2
230
1.3
25
50
40.3
V
oltage (V)
Frequency (Hz)
0
10.4
230
1.3
25
50
57.5
V
oltage (V)
Frequency (Hz)
0
9.2
230
1.5
30
60
40.3
V
oltage (V)
Frequency (Hz)
0
10.4
230
1.5
30
60
57.5
V
oltage (V)
Frequency (Hz)
Table 4.28 High Starting Torque, Settings 8 to B
Setting = 8
50 Hz
Setting = 9
50 Hz
Setting = A
60 Hz
Setting = B
60 Hz
0
12.7
230
1.3 2.5
50
21.9
V
oltage (V)
Frequency (Hz)
0
15
230
1.3 2.5
50
27.6
V
oltage (V)
Frequency (Hz)
0
12.7
230
1.5 3
60
21.9
V
oltage (V)
Frequency (Hz)
0
17.3
230
1.5 3
60
27.6
V
oltage (V)
Frequency (Hz)
4.13 Advanced Drive Setup Adjustments
172