beautypg.com

Emc guidelines compliance – Yaskawa AC Drive Z1000 User Manual

Page 363

background image

Model

Manufacturer: Bussmann

Model

Fuse Ampere Rating (A)

2A0343

FWH-600A

600

2A0396

FWH-600A

600

Three-Phase 400 V Class

4A0005

FWH-40B

40

4A0008

FWH-40B

40

4A0011

FWH-45B

45

4A0014

FWH-45B

45

4A0021

FWH-60B

60

4A0027

FWH-60B

60

4A0034

FWH-125B

125

4A0040

FWH-150B

150

4A0052

FWH-200B

200

4A0065

FWH-225A

225

4A0077

FWH-225A

225

4A0096

FWH-225A

225

4A0124

FWH-250A

250

4A0156

FWH-300A

300

4A0180

FWH-350A

350

4A0240

FWH-400A

400

4A0302

FWH-600A

600

4A0361

FWH-800A

800

4A0414

FWH-800A

800

4A0480

FWH-700A

700

4A0590

FWH-1000A

1000

n

Grounding

The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded

systems, contact your Yaskawa representative for instructions.

n

Guarding Against Harmful Materials

When installing IP00/Open Type enclosure drives, use an enclosure that prevents foreign material from entering the drive

from above or below.

u

EMC Guidelines Compliance

This drive is tested according to European standards IEC/EN 61800-3: 2004.

n

EMC Filter Installation

Note:

Drive models CIMR-Zo2A0011 to 2A0273 and 4A0005 to 4A0302 have a built-in EMC filter.

The following conditions must be met to ensure continued compliance with guidelines.

Refer to EMC Filters on page 367

for EMC filter selection.

Installation Method for CIMR-Zo2A0011 to 2A0273 and 4A0005 to 4A0302

Verify the following installation conditions to ensure that other devices and machinery used with this drive comply with EMC

guidelines.

1.

Move the screws to the ON position to enable the internal EMC filter.

2.

Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.

3.

Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.

Installation Method for CIMR-Zo2A0343, 2A0396, and 4A0361 to 4A0590

Verify the following installation conditions to ensure that other devices and machinery used in combination with this drive

also comply with EMC guidelines.

1.

Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards.

D.2 European Standards

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

363

D

Standards Compliance