11  Technical Data

Installation Manual

SC500HEUS-IA-US_en-14

85

11.2 Torques and Cable Sizes

Required torque values

Connect all cable using copper or aluminium conductors that are suitable for temperatures of
+194°F (+90°C) and in accordiance with National Electrical Code

®

ANSI/NFPA 70 and

Canadian Electrical Code respectively.

Connection method

Cable size

Torque

Cable fixing in screw terminal

4 AWG to 600 kcmil
(25 mm² to 304 mm²)

41.5 ft.-lbs. (56.5 Nm)

Cable lug, aluminum on copper
busbar

4 AWG to 800 kcmil
(25 mm² to 405 mm²)

27.5 ft.-lbs. (37 Nm)

Cable lug, copper on copper
busbar

4 AWG to 800 kcmil
(25 mm² to 405 mm²)

44.5 ft.-lbs. (60 Nm)