8  Electrical Connection

Installation Manual

SC500HEUS-IA-US_en-14

67

8.7.3 Connecting AC cables to busbars

Connecting AC cables to busbars with screw terminals

%"/(&3

High voltages are present in the live components of the low voltage grid.
Death resulting from burning and electric shock.

• Pay close attention to all safety precaution measures regarding the low-voltage grid.
• Switch off the AC and DC circuit breaker and secure it against accidental switching on.
• Ensure that no voltage is present.

$"65*0/

Danger of fire caused by improper connection to the power distribution grid.

• To reduce the risk of fire, do not connect to an AC load center (circuit breaker panel) having

multi-wire branch circuits connected.

$"65*0/

Danger of fire caused by different length of AC cables
Danger of fire.

• Different cable lengths within one phase result in overheating of the shortest cable.
• Connect all AC cables with the same length per phase.