11  Technical Data

Installation Manual

SC500HEUS-IA-US_en-14

83

11 Technical Data

In this section you will find the technical data for the Sunny Central's operation, the norms to which it
conforms and the required cables and torques.

PV Generator Connection Data

Grid Connection Data

General Data

MPP range

330 V DC to 600 V DC at full power

DC Input voltage

330 V DC to 480 V DC at full power

DC starting voltage

390 V DC (adjustable)

Max. input current

1,600 A

DC voltage ripple (peak to peak)

< 3%

Maximum number of DC inputs

9 x PV+/ 9 x PV − / 9 x ground

Maximum number of DC fuses

9 (sized 450 A maximum)

Maximum array short-circuit current
(concerning NEC)

450 A / 1.56 = 288.4 A

Nominal output power up to 113°F (45°C)

500 kW

Output power at 122°F (50°C)

approx. 347 kW

Nominal AC voltage

200 V AC 3 phase without neutral

Operating range

180 to 220 V AC

AC nominal frequency

60 Hz

Operating range

59.3 to 60.5 Hz

Max. AC current

1,470 A AC (at 200 V AC)

Inverter technology

True sine wave, current source, high frequency
PWM with galvanic insulation

Max. operating altitude

13,000 ft. above sea level
Power Reduction:
The Sunny Central can function without power
reduction up to 3,300 ft. above sea level.
At higher altitudes the power is reduced by 5%
per 3,300 ft.