8 Electrical Connection
SMA America, LLC
66
SC500HEUS-IA-US_en-14
Installation Manual
Cable arragement for AC cables longer than 6
1
⁄
2
ft. (2 m)
Arrange the cables as shown in the following figure For all number of cables with length longer than
6
1
⁄
2
ft. (2 m). The description is exemplary for an arrangement with 4 cables per phase.
For AC cable arrangement 1: the distance between the cables should be twice the diameter of of a
single cable.
Figure 2: AC cable arrangement 2
Figure 3: AC cable arrangement 3
/05*$&
The maximum AC cable length between Disconnect Unit and transformer has to be lower than
49 ft. (15 m).
Number of cables
per phase
3
4
5
6
AC cable
arrangement 1.
If possible:
AC cable
arrangement 2.
else:
AC cable
arrangement 1
AC cable
arrangement 1.
If possible: AC
cable
arrangement 3.
else:
AC cable
arrangement 1.