8  Electrical Connection

SMA America, LLC

66

SC500HEUS-IA-US_en-14

Installation Manual

Cable arragement for AC cables longer than 6 

1

2

 ft. (2 m)

Arrange the cables as shown in the following figure For all number of cables with length longer than

1

2

 ft. (2 m). The description is exemplary for an arrangement with 4 cables per phase.

For AC cable arrangement 1: the distance between the cables should be twice the diameter of of a
single cable.

Figure 2: AC cable arrangement 2

Figure 3: AC cable arrangement 3

/05*$&

The maximum AC cable length between Disconnect Unit and transformer has to be lower than
49 ft. (15 m).

Number of cables
per phase

3

4

5

6

AC cable
arrangement 1.

If possible:
AC cable
arrangement 2.
else:
AC cable
arrangement 1

AC cable
arrangement 1.

If possible: AC
cable
arrangement 3.
else:
AC cable
arrangement 1.