5 Transport and Installation
Installation Manual
SC500HEUS-IA-US_en-14
27
5.2 Preparation of the Base
The inverter must be secured to the foundation per local building codes. At the bottom of the
Sunny Central there are 6 mounting holes for anchoring it to its base.
5.2.1 Position of the Mounting Holes
5.2.2 Size of the Mounting Holes
Position
Dimension
Distance between hole 3 and 4
31.69 in. (805 mm)
Distance between hole 1 and 2
53.03 in. (1,347 mm)
Distance between hole 2 and 3
39.37 in. (1,000 mm)
Cable entry width
42.91 in. (1,090 mm)
Cable entry depth
31.69 in. (805 mm)
Position
Dimension
Diameter
0.63 in. (16 mm)