beautypg.com

2 opening the power cabinet – SMA SC 500HE-US Installation User Manual

Page 82

background image

10  Opening the Sunny Central

SMA America, LLC

82

SC500HEUS-IA-US_en-14

Installation Manual

16. Disconnect the grounding cable inside the metal plate.
17. Put the metal plate aside.
18. Verify the absence of voltage with respect to ground at the AC clamp with an appropriate

meter.
☑ If there is a voltage present, the installation must be checked.

19. Verify the absence of voltage with respect to ground at the DC clamp with an appropriate

meter.
☑ If there is a voltage present, the installation must be checked.

10.2 Opening the Power Cabinet

1. Switch off the Sunny Central as described in section 10.1.
2. Pull the handle of the Power Cabinet upwards and

turn it to the right.

3. Put the key into the Power Cabinet's lock and open

it.

4. Open the door.

5. Inside of the left door is a handle (A). Turn the

handle through 180° to the top left.
☑ The door‘s catch is released and the left door of

the Power Cabinet can be opened.

6. Open the left door of the Power Cabinet.

This manual is related to the following products: