beautypg.com

6 connection of the pv modules, Connection at positive grounding – SMA SC 500HE-US Installation User Manual

Page 62

background image

8  Electrical Connection

SMA America, LLC

62

SC500HEUS-IA-US_en-14

Installation Manual

8.6 Connection of the PV Modules

Do not connect the PV modules until the optional communication cables have been connected
(see section 7). DC distribution boxes (e.g. Sunny Central String-Monitor) must be installed between
the PV modules and the Sunny Central, where the PV module cables are gathered and led to the
Sunny Central.
The Photovoltaic System Grounding must be installed per the requirements of Sections 690.41
through 690.47 of the National Electrical Code, ANSI/NFPA 70 and is the responsibility of the
installer.

8.6.1 PV Modules: DC − Connection at Negative Grounding and

DC+ Connection at Positive Grounding

Connection with Terminal Blocks

The illustration below shows a Sunny Central which is equipped for connection to 9 or 18 DC strings.

1. Strip the cable by about 1.2 in. (30 mm).
2. Open the screw terminal completely.

3. Plug the copper inner conductor of the cable into

the screw terminal.

4. Tighten the screw terminal using a screwdriver.

The required torque is 315 in-lb.

5. Connect all grounded DC path cables of the PV

modules as described above.



A

Screw terminals for the connection of the PV modules'
grounded DC path cables.

1.2 in.

This manual is related to the following products: