Troubleshooting and Problem Solving

SMA Solar Technology AG

90

SC-BEN100262

User Manual

222

Error text:
Ambient temperature

Error type 2

Cause of error:
The ambient temperature is higher than 51 °C.
Corrective measure:

• Check the cooling concept.
• Check the fans.
• Check the ambient conditions.
• Check the sensor.

400

Error text:
internal failure of inverter bridge

Error type
2/3

Cause of error:
Internal inverter bridge fault (e.g. symmetry fault, board voltage, undertemperature, sensor
broken).
Corrective measures:
If this error occurs frequently, contact the SMA Serviceline.

402

Error text:
ser. com. with inverter bridge disturbed

Error type 2

Cause of error:

• The RS485 communication between the inverter bridge and the Sunny Central Control

is interrupted.

• The inverter bridge or the Sunny Central Control may be faulty.

Corrective measures:

• Check the RS485 wiring.
• If this is a permanent error, please contact the SMA Serviceline.

408

Error text:
PV Overvoltage

Error type 3

Cause of error:
DC voltage is too high on the generator side.
Corrective measures:

• Immediately disconnect the PV generator from the Sunny Central! Danger of damage

to the Sunny Central!

• Check DC voltage.
• Check module wiring and system design.