SMA SC 200 User Manual
Page 85
SMA Solar Technology AG
Troubleshooting and Problem Solving
User Manual
SC-BEN100262
85
602
Error text:
Defective default Reactive power
Error type 1
Cause of error:
The current value at the analog input is not within the permissible range.
Corrective measures:
• Check the analog input.
603
Error text:
Disturbed communication Effective power
Error type 1
Cause of error:
The setpoint signal at the communication level is faulty.
Corrective measures:
• Check the communication route.
604
Error text:
Disturbed communication Reactive power
Error type 1
Cause of error:
The setpoint signal at the communication level is faulty.
Corrective measures:
• Check the communication route.
680
Error text:
External Alarm was initiated
Error type 1
Cause of error:
Dependent on the monitored unit.
Corrective measures:
Check the unit connected to the external alarm input.
681
Error text:
Reduction of effective power activated
Error type 1
Description:
The Sunny Central is currently reducing active power by means of an external setpoint.
No.
Description