2 access to configuration, Access to configuration – SMA SC 200 User Manual
Page 65

SMA Solar Technology AG
External Grid Monitoring Relay (optional)
User Manual
SC-BEN100262
65
12.3.2 Access to Configuration
Password protection
You will need a password to carry out any parameter settings / adjustments. Once you have entered
this password, you can view and adjust all parameters.
The factory setting for the password is <4753>.
You are free to change the password as desired. Keep the password safe to prevent any
unauthorized parameter adjustments.
Enter Password
Change password
DANGER!
Danger to life through changing the internal safety specifications of the Sunny
Central.
• Only qualified electricians may carry out parameter adjustments.
• Only adjust parameters after consultation with the SMA Serviceline.
Enter code number 0000 - 9999
Input screen for the password
Password Protection ON / OFF
ON = Password protection is activated.
OFF = Password protection is deactivated.
Define password for code level 1
The password is preset to: CS1 = 0001
Define password for code level 2
The password is preset to: CS2 = 4753