Parameters

SMA Solar Technology AG

38

SC-BEN100262

User Manual

7.2 Default Parameter Settings

The following table gives a summary of the main operating parameters. It includes the adjustable
range and default value of each parameter. The adjustable range and default value depend on the
Sunny Central model.
The parameters marked with * can only be displayed / changed after entering the installer password
(see Section 5.6 ”Enter Password” (page 27)).

Parameters

Area

Normal

VmppMin *

450 ... 880 V
(SC 200 / SC 250 / SC 350 / SC 500)
540 ... 880 V (SC 560)

250 V (SC 100LV)
300 V (SC 125LV)
450 V (SC 500HE / SC 350HE /
SC 350 / SC 250HE / SC 250 /
SC 200HE / SC 200 / SC 150)
540 V (SC 560)

dVreference * 5 V ... 200 V

80 V

PsearchMpp * 0 ... 25000 W

device-specific setting

TsearchMpp * 60 ... 3600 s

600 s

dVtrack *

1 ... 10 V

5 V/TaMp

TcheckMpp * 10 ... 60 s

10 s

Mpp Factor * 0.20 ... 1.00

0.80

TrackCnt *

5 ... 20

7

VpvStart

200 ... 1000 V

400 V (SC 100LV / SC 125LV)
600 V (SC 500HE / SC 350HE /
SC 350 / SC 250HE / SC 250 /
SC 200HE / SC 200 / SC 150)
650 V (SC560HE)

Tstart

1 ... 600 s

90 s

Twait

0 ... 1800 s

600 s

PpvStop

0 ... 10000 W

device-specific setting

Tstop

1 ... 300 s

60 s

Pac max *

1 ... 1000 kW

device-specific setting

TMax. cabinet 30 ... 70 °C

50 °C

TMin. cabinet -30 ... 10 °C

-20 °C