2 default parameter settings, Default parameter settings – SMA SC 200 User Manual
Page 38
![background image](https://www.manualsdir.com/files/818949/content/doc038.png)
Parameters
SMA Solar Technology AG
38
SC-BEN100262
User Manual
7.2 Default Parameter Settings
The following table gives a summary of the main operating parameters. It includes the adjustable
range and default value of each parameter. The adjustable range and default value depend on the
Sunny Central model.
The parameters marked with * can only be displayed / changed after entering the installer password
(see Section 5.6 ”Enter Password” (page 27)).
Parameters
Area
Normal
VmppMin *
450 ... 880 V
(SC 200 / SC 250 / SC 350 / SC 500)
540 ... 880 V (SC 560)
250 V (SC 100LV)
300 V (SC 125LV)
450 V (SC 500HE / SC 350HE /
SC 350 / SC 250HE / SC 250 /
SC 200HE / SC 200 / SC 150)
540 V (SC 560)
dVreference * 5 V ... 200 V
80 V
PsearchMpp * 0 ... 25000 W
device-specific setting
TsearchMpp * 60 ... 3600 s
600 s
dVtrack *
1 ... 10 V
5 V/TaMp
TcheckMpp * 10 ... 60 s
10 s
Mpp Factor * 0.20 ... 1.00
0.80
TrackCnt *
5 ... 20
7
VpvStart
200 ... 1000 V
400 V (SC 100LV / SC 125LV)
600 V (SC 500HE / SC 350HE /
SC 350 / SC 250HE / SC 250 /
SC 200HE / SC 200 / SC 150)
650 V (SC560HE)
Tstart
1 ... 600 s
90 s
Twait
0 ... 1800 s
600 s
PpvStop
0 ... 10000 W
device-specific setting
Tstop
1 ... 300 s
60 s
Pac max *
1 ... 1000 kW
device-specific setting
TMax. cabinet 30 ... 70 °C
50 °C
TMin. cabinet -30 ... 10 °C
-20 °C