Troubleshooting and Problem Solving
SMA Solar Technology AG
86
SC-BEN100262
User Manual
15.1.4 Faults
No.
Description
104
Error text:
No Grid Synchronization
Error type 3
Cause of error:
Left-hand rotating field or internal device fault.
Corrective measures:
• Check (right-hand) rotating field.
• Check whether all internal fuses are switched on.
• Contact the SMA Serviceline.
105
Error text:
Grid voltage to low
Error type 2
Cause of error:
Voltage on the AC side is below the permitted range.
Corrective measures:
• Check the grid connections.
• Check grid stability.
106
Error text:
Grid voltage to high
Error type 2
Cause of error:
Voltage on the AC side is above the permitted range.
Corrective measures:
• Check the grid connections.
• Check grid stability.
110
Error text:
UVW-Range
Error type 2
Cause of error:
Voltage on phase L1, L2, or L3 outside the permitted range.
Corrective measures:
• Check the grid connections.
• Check grid stability.