Troubleshooting and Problem Solving

SMA Solar Technology AG

86

SC-BEN100262

User Manual

15.1.4 Faults

No.

Description

104

Error text:
No Grid Synchronization

Error type 3

Cause of error:
Left-hand rotating field or internal device fault.
Corrective measures:

• Check (right-hand) rotating field.
• Check whether all internal fuses are switched on.
• Contact the SMA Serviceline.

105

Error text:
Grid voltage to low

Error type 2

Cause of error:
Voltage on the AC side is below the permitted range.
Corrective measures:

• Check the grid connections.
• Check grid stability.

106

Error text:
Grid voltage to high

Error type 2

Cause of error:
Voltage on the AC side is above the permitted range.
Corrective measures:

• Check the grid connections.
• Check grid stability.

110

Error text:
UVW-Range

Error type 2

Cause of error:
Voltage on phase L1, L2, or L3 outside the permitted range.
Corrective measures:

• Check the grid connections.
• Check grid stability.