Troubleshooting and Problem Solving

User Manual

SC-BEN100262

83

380

Error text:
SMU

Error type 1

Cause of error:
The string monitoring system has detected one or more faulty strings or surge voltage
protectors.
Corrective measures:

• Under "Device Set-up > SMUs > Devices > Measured Values", read out the individual

string currents to locate the faulty string.

• More detailed information can be found in the Sunny String-Monitor manual.

381

Error text:
ser. com. with SMU disturbed

Error type 1

Cause of error:
Communication failure between Sunny Central and the Sunny String-Monitors.
Corrective measures:

• Check communication lines and connections.
• More detailed information can be found in the Sunny String-Monitor manual.

382

Error text:
thievery solar panel

Error type 1

Cause of error:
Signal loop for theft detection at the Sunny String-Monitor has been interrupted.
Corrective measures:

• Check string currents.
• Check signal loop.
• For further details, refer to the installation guide and user manual of the Sunny String-

Monitor and / or Sunny String-Monitor Cabinet.

585

Error text:
ser. com. with team disturbed

Error type 1

Cause of error:
The communication between the two team inverters has failed.
Corrective measures:

• Check the RS485 wiring for team communication.
• Check power supply of the team member.
• Check team parameters at both Sunny Centrals.