Troubleshooting and Problem Solving

User Manual

SC-BEN100262

89

217

Error text:
DC CB tripped or door switch open

Error type 2

Cause of error:

• The cabinet door was opened during operation.
• The DC circuit breaker has tripped due to an internal fault.
• The reverse current monitoring system on the DC side has tripped.

Corrective measures:

• Close the cabinet doors.
• Check the function of the door switches.
• Check the function and activation of the emergency shut-off relay.
• Check reverse current monitoring.
• Contact the SMA Serviceline.

220

Error text:
Release- or Reset-Signal faulty

Error type 2

Cause of error:
The inverter bridge release or clearance signal is defective.
Corrective measures:
If this is a permanent error, please contact the SMA Serviceline.

221

Error text:
CHOPPER Overtemperature

Error type 3

Cause of error:

• EVR resistor overtemperature.
• Defective chopper module.
• After 90 minutes, the inverter will attempt to restart.

Corrective measures:

• Check resistor for dirt.
• Make sure resistor is sufficiently ventilated.
• Contact the SMA Serviceline.