5 team mode interrupted, Team mode interrupted – SMA SC 200 User Manual
Page 77

SMA Solar Technology AG
Sunny Team (optional)
User Manual
SC-BEN100262
77
14.5 Team Mode Interrupted
An interruption of team operation can have various causes. These will be described in this section.
Key switch set to "STOP"
If one of the two Sunny Centrals is switched off, team operation is not possible. The Sunny Centrals
connect individually to the grid.
Emergency shut-off switch actuated
Depending on the wiring option, the emergency shut-off switches of the Sunny Centrals in team
operation are either interconnected or not interconnected. SMA Solar Technology recommends
connecting the emergency shut-off switches of both Sunny Centrals in the team.
• Emergency shut-off switches electrically interconnected:
– Both Sunny Centrals change to "Emergency shut-off" mode. Neither grid feed nor team
operation is possible.
• Emergency shut-off switches not interconnected, no team operation.
– The Sunny Central with the emergency shut-off switch actuated switches to "Emergency shut-
off" mode.
– If the second Sunny Central is the team manager, it willl remain in its current operating mode.
Team operation is not possible.
• Emergency shut-off switches not interconnected, team operation.
– The Sunny Central with the emergency shut-off switch actuated switches to "Emergency shut-
off" mode.
– The second Sunny Central is the team manager and was in "Wait" mode. It feeds the energy
from its PV generator into the public grid. Team operation is not possible.
– The second Sunny Central is the team manager and was not in "Wait" mode. Neither grid
feed nor team operation is possible.