beautypg.com

3 parameters, 4 monitoring, Parameters – SMA SC 200 User Manual

Page 66: Monitoring

background image

External Grid Monitoring Relay (optional)

SMA Solar Technology AG

66

SC-BEN100262

User Manual

12.3.3 Parameters

Voltage measurement

Voltage transformer configuration

Adjust the setting for the primary voltage transformer to the medium-voltage value to match your
system. This setting has no effect on monitoring, but only on the display of voltage readings.

12.3.4 Monitoring

This parameter is masked out as soon as you have set the "voltage measurement" parameter to three-
wire system.
When setting the voltage thresholds please note the following:

• Sunny Central with integrated transformer: set the threshold values as absolute values in volts,

corresponding to those present at the grid connection.

Voltage measurement
Four-wire system / three-wire system
Do not change

Voltage transformer secondary
Device-specific presetting, do not change.

Voltage transformer primary
For Sunny Central devices without an integrated
transformer, enter the voltage of the medium-voltage
side (e.g. 20 kV).
For Sunny Central devices with an integrated
transformer, this parameter is preset according to the
specific device and the setting must not be
changed.

Monitoring for...
Three-wire / four-wire system; default for Sunny
Central with integrated transformer: four-wire
system; default for Sunny Central without
integrated transformer: three-wire system
Do not change

This manual is related to the following products: