5 features, 6 electronic solar switch, 7 torques – SMA SB 2500TL-21 Installation User Manual
Page 89: 8 grid configuration, Features, Electronic solar switch, Torques, Grid configuration

SMA Solar Technology AG
Technical Data
Installation Manual
SB25-30TLST-21-IA-en-13
89
13.5 Features
13.6 Electronic Solar Switch
13.7 Torques
13.8 Grid Configuration
DC connection
SUNCLIX DC connector
AC connection
spring clamp terminal
Display
LC graphic display
Bluetooth
as standard
RS485, galvanically isolated
optional
Multi-function relay
optional
Electronic Solar Switch
optional
Electrical endurance in the event of short circuit,
at nominal current 35 A
at least 50 switching processes
Maximum switching current
35 A
Maximum switching voltage
800 V
Maximum PV power
12 kW
Degree of protection when plugged in
IP65
Degree of protection when unplugged
IP21
Fuses for Electronic Solar Switch
F200, 600V/4A, fast and
F201, 600V/4 A, fast
(both soldered, not replaceable)
Upper enclosure lid screws
6.0 Nm
Lower enclosure lid screws
2.0 Nm
Additional earth terminal
6.0 Nm
SUNCLIX swivel nut
2.0 Nm
RS485 interface fastening screw
1.5 Nm
Multi-function relay fastening screw
1.5 Nm
TN-C
suitable
TN-S
suitable
TN-C-S
suitable
TT, if V
N_PE
< 15 V
suitable