Troubleshooting

Installation Manual

SB25-30TLST-21-IA-en-13

71

3701

Resid.curr.too.high The inverter has detected residual current and interrupts feed-in

operation.
Corrective measures:

• Check strings for earth faults (see Section 11.5 "Checking

the PV Array for Earth Faults" (page 76)).

• The installer of the PV array must remedy the earth faults

before you re-connect the affected string.

Check generator

3801 to
3802

DC overcurrent

The inverter switches off due to an overcurrent on the DC side.
Corrective measures:
If this event occurs frequently:

• Check the design and the circuitry of the PV array.

Check generator

3901 to
3902

Waiting for DC
start conditions

The input power or voltage of the PV modules is not yet sufficient
for feeding into the electricity grid.
Corrective measures:

• Wait until irradiation is higher.
• If this event recurs at medium irradiation levels, check the

PV plant design and the correct circuitry of the PV array.

Start cond. not met

6001 to
6438

Self diagnosis

Internal device fault. The inverter interrupts feed-in operation.
Corrective measures:

• Contact the SMA Service Line (see Section 15 "Contact"

(page 92)).

Interference device

6501 to
6502

Self diagnosis

The inverter interrupts feed-in operation due to interior
overheating.
Corrective measures:

• Ensure sufficient ventilation.
• Check the heat dissipation (see Section 9.2 "Checking

Heat Dissipation" (page 62)).

Overtemperature

6603 to
6604

Self diagnosis

The inverter has detected an internal overload and interrupts
feed-in operation.
Corrective measures:

• Contact the SMA Service Line (see Section 15 "Contact"

(page 92)).

Overload

Event no. Message

Cause and corrective measures