3 protective devices, 4 climatic conditions, Protective devices – SMA SB 2500TL-21 Installation User Manual

Page 88: Climatic conditions

background image

Technical Data

SMA Solar Technology AG

88

SB25-30TLST-21-IA-en-13

Installation Manual

*EN 50438: Does not apply to all country standard deviations of EN 50438
IEC 62109-2: In order to meet the requirements of this standard, the inverter must either be equipped with a multi-function relay

used as a fault indication relay or there must be a connection to Sunny Portal with the fault alarm via e-mail activated.
RD 1699:2011 and RD 661/2007: Contact the SMA Service Line for restrictions in specific regions.
NRS 97-1-2: This standard stipulates that a special label be attached to the AC distribution board to draw attention to the AC-side

disconnection of the inverter in the case of grid failure (for more details, see NRS 97-1-2, Sec. 4.2.7.1 and 4.2.7.2)

13.3 Protective Devices

*optional

13.4 Climatic Conditions

As per IEC 60721-3-4, Installation type C, Class 4K4H

As per IEC 60721-3-2, transport type E, Class 2K3

Approvals, as per 03/2013*

AS 4777, CEI 0-21, C10/11, DIN EN 62109-1,

EN 50438, G59/2, G83/1-1,

IEC 61727 (PEA), IEC 62109-2,

NEN EN 50438, NRS 97-1-2, PPC, PPDS,

RD 1699:2011, RD661/2007,

UTE C15-712-1, VDE 0126-1-1,

VDE-AR-N 4105

DC reverse polarity protection

short-circuit diode

Input-side load disconnect unit*

Electronic Solar Switch

DC overvoltage protection

thermally monitored varistors

AC short-circuit current capability

current control

Grid monitoring

SMA Grid Guard 3

Maximum permissible fuse protection

25 A

Earth fault monitoring

insulation monitoring: R

iso

> 625 k Ω

All-pole sensitive residual-current monitoring unit

available

Extended temperature range

− 25°C to +60°C

Extended humidity range

0% to 100%

Extended air pressure range

79.5 kPa to 106 kPa

Temperature range

− 25°C to +70°C