Efficiency
13.2 General Data
AC mains frequency*
50 Hz/60 Hz
Operating range at AC mains frequency 50 Hz
45 Hz to 55 Hz
Operating range at AC mains frequency 60 Hz
55 Hz to 65 Hz
Displacement power factor, adjustable
0.8
overexcited
to 1 to 0.8
underexcited
Feed-in phases
1
Connection phases
1
Overvoltage category as per IEC 60664-1
III
Maximum efficiency, η
max
97.0%
European weighted efficiency, η
EU
96.1%
Width x height x depth, without
Electronic Solar Switch
490 mm x 488 mm x 185 mm
Width x height x depth with
Electronic Solar Switch
490 mm x 519 mm x 185 mm
Weight
23 kg
Length x width x height of packaging
597 mm x 617 mm x 266 mm
Transport weight
26 kg
Climatic category as per IEC 60721-2-1
4K4H
Environment category
Outdoors
Pollution degree outside the enclosure
3
Pollution degree inside the enclosure
2
Operating temperature range
− 25°C to +60°C
Maximum permissible value for relative humidity,
non-condensing
100%
Maximum operating altitude above MSL
2,000 m
Noise emission (typical)
≤ 25 dB(A)
Power loss in night mode
< 1 W
Topology
transformerless
Cooling concept
convection
Degree of protection for electronics according to
IEC 60529
IP65
Connection area degree of protection according
to IEC 60529
IP54
Protection class according to IEC 62103)
I