SMA SB 2500TL-21 Installation User Manual
Page 48

Electrical Connection
SMA Solar Technology AG
48
SB25-30TLST-21-IA-en-13
Installation Manual
If the inverter is not set to the country of installation, there are several ways of configuring the required
country standard:
• Setting via the two rotary switches (see Section 6.5.2 "Setting the Country Standard and
Language using the Rotary Switches" (page 49)).
• Alternatively you can conduct the settings via the "CntrySet" or "Set country standard"
parameters via a communication product, once you have commissioned the inverter.
• If you require adjusted parameter settings for your installation site, you can change these with
the help of a communication product.
E
0
Off-Grid 50 Hz*
English
no
flexible
E
1
Off-Grid 50 Hz*
German
no
flexible
E
2
Off-Grid 50 Hz*
French
no
flexible
E
3
Off-Grid 50 Hz*
Spanish
no
flexible
E
4
Off-Grid 50 Hz*
Italian
no
flexible
E
5
Off-Grid 50 Hz*
Greek
no
flexible
E
6
Off-Grid 50 Hz*
Czech
no
flexible
a)
Setting in accordance with VDE-AR-N-4105 for PV plants ≤ 3.68 kVA (Germany)
b)
Setting in accordance with VDE-AR-N-4105 for PV plants > 3.68 kVA and < 13.8 kVA (Germany)
c)
Setting in accordance with VDE-AR-N-4105 for PV plants > 13.8 kVA (Germany)
d)
Setting in accordance with CEI 0-21 for PV plants ≤ 6 kW (Italy)
e)
Setting in accordance with CEI 0-21 for plants with external grid and plant protection > 6 kW (Italy)
*
Planned
(A) (B) Country data set
Display language
Grid Guard
protection
Country