8  Troubleshooting

Operating Manual

PPC-BE-P7-en-13

45

A value specified in the

Modbus profile is not being

transmitted by the

Power Plant Controller to the

devices in the system.

The Modbus configuration may be incorrect.

Corrective measures:

• Check the Modbus configuration using the assignment tables and adjust if required

(see Section 7.7, page 33).

The setpoint specification may have been set to local.

Corrective measures:

• Ensure that the setpoint is set to Remote.

Problem

Cause and corrective measures