Page 14

background image

3  Product Overview

SMA Solar Technology AG

14

PPC-BE-P7-en-13

Operating Manual

For each instantaneous value, the field Active values indicates whether the default value or the redundant value is used.

3.4.3 "PPC"

Menu field

Explanation

Overview

Displays the number of all installed Sunny Centrals and Cluster Controllers in the entire PV system,

as well as the number of connected and inaccessible devices

Instantaneous

values

Provides an overview of instantaneous values of the Sunny Centrals, Cluster Controllers and

network analyzers

Settings

In this area, the following settings can be displayed and adjusted:

Type label: provides unchanging, service-relevant information which is required if faults have

occurred

Device: User interface language and Power Plant Controller time settings
Access control: Passwords of the user groups
System communication: IP addresses of Power Plant Controllers, Sunny Centrals,

Cluster Controllers and Inverter Managers as well as activating and deactivating the

communication

Modbus server: Configuration of the Modbus server (installer mode only)

Grid management

services

In this area, the following settings can be adjusted:

Device table inverters: IP addresses of the Sunny Centrals and configuration of the

communication between the Sunny Centrals and the Power Plant Controller (installer mode

only)

Device table Modbus gateways: IP addresses of the Cluster Controller and

Inverter Manager as well as configuration of the communication between these devices and

the Power Plant Controller (installer mode only)

Device table PPC Slave: IP addresses of the Power Plant Controller slaves and the type of

slave operation as well as grouping of the slaves

Device table Power analyzers: Configuration of the network analyzers and entry of the

corresponding IP address (installer mode only)

Setpoint: Change of setpoint mode from Remote (Modbus protocol or analog values) to

Local (fixed setpoint) and entry of the fixed setpoints for active power and reactive power

with local setpoint transmission (installer mode only)

Input signals: Selection and scaling of the signals sent from the point of interconnection to

the Power Plant Controller

Events

Displays all the errors and warnings that have occurred

The errors and warnings are acknowledged here.

Backup and

restore

Enables the current configuration of the Power Plant Controller to be saved or updated via SD

memory card